Continuous Emission Monitoring Systems (CEMS)
CEMS for Iron and Steel Mills (Ferrous Metals)
Continuous emission monitoring system for iron and steel mills, combining extractive gas analysers, in-situ gas analysers and in-situ particulate analysers to measure SO2, NO2 and total PM from sinter plants, coke ovens and furnaces.

This continuous emission monitoring system (CEMS) for iron and steel mills measures sulphur dioxide (SO2), nitrogen dioxide (NO2) and total particulate matter (PM) at the stack. Depending on the source, it combines extractive gas analysers, in-situ gas analysers and in-situ particulate analysers. Readings pass to a CEMS data interface system (DIS) and on to the DOE server over TCP/IP, supporting compliance with the emission limit values that apply to the production and processing of ferrous metals.
Features
- Covers sinter plants, coke ovens, blast furnaces (regenerator), basic oxygen furnaces (converter gas) and electric arc furnaces
- Extractive and in-situ gas analysers for SO2 and NO2
- In-situ particulate analysers for total PM / dust
- Data acquisition system (DAS) and data interface system (DIS)
- 4–20 mA signals to the CEMS-DIS and TCP/IP link to the DOE server
How it works
- SO2, extractive: NDIR, NDUV, GFC, FTIR, PAS or fluorescence
- SO2, in-situ: DOAS, GFC or FTIR
- NO2, extractive: NDUV, PAS or fluorescence; in-situ: DOAS
- Total PM / dust, extractive: light scatter or beta absorption
- Total PM / dust, in-situ: transmissometry, triboelectric, double pass or single pass
Emission limit values (mg/m³)
- Sinter plants (waste gas from the sintering belt): SO2 500, NO2 400, total PM 50
- Coke ovens: total PM 10, at 5% O₂
- Blast furnace (regenerator): total PM 50, at 3% O₂
- Basic oxygen furnace (converter gas) and electric arc furnaces: total PM 50
Applications
- Iron and steel mills
- Sinter plants and coke ovens
- Blast, basic oxygen and electric arc furnaces
DOE requirements
- Supplier listed as an appointed and approved company on the DOE website
- Data acquisition system (DAS) and data interface system (DIS)
LKS supplies CEMS for iron and steel mills in Malaysia, with installation, calibration and after-sales support. Contact our engineers for a system proposal.
Specifications
| Item | Details |
|---|---|
| System type | Continuous emission monitoring system (CEMS) |
| Analyser types | Extractive gas analysers, in-situ gas analysers, particulate in-situ analysers |
| Measured parameters | SO2, NO2, total PM / dust |
| SO2 principle (extractive) | NDIR, NDUV, GFC, FTIR, PAS, fluorescence |
| SO2 principle (in-situ) | DOAS, GFC, FTIR |
| NO2 principle (extractive) | NDUV, PAS, fluorescence |
| NO2 principle (in-situ) | DOAS |
| Dust principle (extractive) | Light scatter, beta absorption |
| Dust principle (in-situ) | Transmissometry / triboelectric, double pass, single pass |
| Data systems | Data acquisition system (DAS), data interface system (DIS) |
| Signal links | 4–20 mA to CEMS-DIS; TCP/IP to DOE server |
Download the CEMS for Iron and Steel Mills (Ferrous Metals) catalogue (PDF)
Products
Equipment for this application.

Multigas Analyzer
Multigas analyzers for flue gas and process gas, measuring SO2, NOx, CO, CO2, O2, NH3 and more by UV DOAS, NDIR, TDLAS or electrochemical principles, with Modbus outputs.View range
Dust & Opacity Analyzers
Dust and opacity analyzers for continuous particulate monitoring in stacks and ducts, using transmittance, scattered light, backscatter, extractive and triboelectric principles.View range
Read next
Related topics.
01CEMS for Power Plants
Continuous emission monitoring system (CEMS) for power plant boilers and combustion turbines above 10 MWe, combining extractive and in-situ gas analysers with a particulate analyser to measure SO2, NO2, CO and total PM.Read more
02CEMS for Cement Plants
Continuous emission monitoring system (CEMS) for cement kilns and related non-metallic sources, combining extractive and in-situ gas analysers with a particulate in-situ analyser to measure SO2, NO2 and total PM/dust against DOE emission limits.Read more
03CEMS for Oil and Gas: Refineries and Natural Gas Facilities
Continuous emission monitoring system (CEMS) for oil and gas refineries and natural gas processing and storage facilities, combining extractive and in-situ gas analysers with a particulate analyser to measure SO2 and total PM.Read more
04CEMS for Palm Oil Mills
Continuous emission monitoring system (CEMS) for palm oil mills, combining extractive gas analyzers, in-situ gas analyzers and particulate in-situ analyzers to measure total PM/dust and opacity, with data sent to the DOE server.Read more
05CEMS for Waste Incinerators
Continuous emission monitoring system (CEMS) for waste incinerators of all sizes, combining extractive and in-situ gas analysers with an in-situ particulate analyser to measure total PM, NMVOC, HCl, HF, SO2, NO2 and CO against DOE emission limits.Read more
06CEMS for Non-Ferrous Metal Plants
Continuous emission monitoring system (CEMS) for sinter plants and non-ferrous metal production, using extractive and in-situ gas analysers and a particulate in-situ analyser to measure SO2, NO2 and total PM/dust.Read more
Lifecycle support
Installed, calibrated and maintained.
With more than two decades in valves and instrumentation across a diverse range of industries, we keep instruments accurate and valves healthy, because valve health management is vital for plant safety.
- Installation & commissioning
- Calibration & testing
- Maintenance & overhaul
- Dismantling & replacement
Get in touch
Need a quote or technical advice?
Tell us about your application and our engineers will recommend the right instrument or system.
- 01Share your applicationProcess, medium, range and site conditions.
- 02Engineer recommendationWe match the right instrument or system to your process.
- 03Quotation and supportSupply, installation, calibration and after-sales service.