Surge Protection Devices

Class I Surge Protection Device LP-50A

Model LP-50A

LP-50A Class I surge protection device for the low-voltage side of 230/400 V transformers or the LPZ0–LPZ1 boundary, with 25 kA impulse discharge current (10/350 µs), < 2.0 kV protection level and 2P to 4P combinations.

Overview

About the Class I Surge Protection Device LP-50A.

The LP-50A is a Class I surge protection device fitted on the low-voltage side of a transformer with a rated working voltage of 230/400 V, or at the boundary between lightning protection zones LPZ0 and LPZ1. It protects the installation against overvoltage caused by lightning or surges. Built-in multi-gap construction gives a large current capacity and a low residual voltage in a fully enclosed housing with no arc escape. The device is not intended for systems whose expected short-circuit current exceeds its rated breaking follow current, and a backup fuse must be connected on its supply side.

Features

  • Impulse discharge current Iimp 25 kA (10/350 µs) with a voltage protection level below 2.0 kV
  • Large current capacity, low residual voltage, totally enclosed structure with no arc escape
  • Built-in multi-gap design with a strong ability to extinguish follow current
  • Protection modes L-N, L-PE and N-PE
  • Combinations 2P, 3P, 4P and 3P+NPE for different power networks
  • Flame-retardant reinforced nylon housing (UL 94V-0)
  • 100 ns response time

Applications

  • Low-voltage side of 230/400 V distribution transformers
  • Main incoming supplies at the LPZ0 / LPZ1 zone boundary
  • Class I lightning and surge protection of low-voltage power networks

LKS supplies the LP-50A surge protection device in Malaysia, with installation and after-sales support. Contact our engineers for protection-scheme selection and a quotation.

  • Surge protection
  • Lightning protection

Specifications

ModelLP-50A
ClassClass I
Rated working voltage230/400 V
Max. continuous operating voltage320 V
Voltage protection level Up< 2.0 kV
Impulse discharge current Iimp (10/350 µs)25 kA
Response time100 ns
Protection modesL-N, L-PE, N-PE
Combination mode2P, 3P, 4P, 3P+NPE
Insulation resistance> 5 MΩ
Max. backup fuse (if mains > 250 A)250 A gL
Recommended grounding conductor16 mm² multi-strand flexible wire
Housing materialFlame-retardant reinforced nylon (UL 94V-0)
Dimensions (drawing)36 mm width per pole (1P 36, 2P 72, 3P 108, 4P 144 mm); 93 mm height; 66.5 mm depth

Lifecycle support

Installed, calibrated and maintained.

With more than two decades in valves and instrumentation across a diverse range of industries, we keep instruments accurate and valves healthy, because valve health management is vital for plant safety.

  • Installation & commissioning
  • Calibration & testing
  • Maintenance & overhaul
  • Dismantling & replacement

Get in touch

Need a quote or technical advice?

Tell us about your application and our engineers will recommend the right instrument or system.

  1. 01Share your applicationProcess, medium, range and site conditions.
  2. 02Engineer recommendationWe match the right instrument or system to your process.
  3. 03Quotation and supportSupply, installation, calibration and after-sales service.